How much power a hybrid inverter burns while doing nothing

Planted Czytaj po polsku →

I run a small PV system – 2.5 kWp on microinverters – that mainly covers the house’s daytime use. A friend with a bigger setup (about 5 kWp, also on microinverters) added a home battery with a hybrid inverter (a Deye, if I remember right) and mentioned that the inverter alone draws 80–120 W, depending on what it is doing.

The datasheet gave no figure for self-consumption. Online, everyone calculates how much energy you can store and get back, but almost nobody asks how much the device uses just to keep itself running.

The scale of it

100 W sounds harmless, but it runs around the clock:

  • 2.4 kWh a day,
  • about 72 kWh a month,
  • about 876 kWh a year.

My house uses about 6 kWh a day, so the inverter idling alone would be 40% of that.

What specific devices draw

Manufacturers rarely publish self-consumption, so I collected the numbers forum users reported. These are individual measurements, not datasheet values:

DeviceReported self-consumption
Deye 10 kW with batteryabout 75 kWh a month (~2.5 kWh a day)
FoxESS 5 kWabout 170 W while working; 23–45 W on standby (the maker says 15 W)
Sumry 10 kW5–10 W when running from the grid, 40–80 W from the battery
Easun iSolar SMG II 4 kW25–60 W from the grid, 70–80 W under normal load

Victron reportedly has the lowest self-consumption, but its price kills the business case for a system this small. Switching the inverter off at every passing cloud does not help either – waking up from standby usually takes tens of seconds.

When a battery next to PV makes sense

I scaled my winter production up to a system four times bigger (10 kWp) and subtracted 75 kWh a month for running the battery:

Month10 kWp productionAfter subtracting 75 kWh
November168 kWh+93 kWh
December108 kWh+33 kWh
January137 kWh+62 kWh

With 10 kWp on the roof there is something left over even in winter. With my 2.5 kWp – 27 to 42 kWh a month in those months – the inverter alone would eat more than the panels produce.

What about a battery charged only on the cheap tariff?

I also worked out the case without PV: charge in the cheap zone, use in the expensive one. Energa gross prices from February 2025:

  • G12r: 0.47 PLN/kWh in the cheap zone and 1.04 PLN/kWh in the expensive one,
  • G11: 0.77 PLN/kWh around the clock.

I assume about 30% losses on charging and discharging, including the battery’s own consumption. A cheap kWh then really costs about 0.61 PLN, 16 grosz less than on G11 – that is what I earn on every kWh that passes through the battery. The inverter idling costs 2.4 kWh × 0.61 PLN ≈ 1.46 PLN a day. To break even, at least about 9.15 kWh a day has to pass through the battery. I use 6 kWh, so for me it does not add up.

Takeaways

  • Inverter self-consumption belongs in any battery payback calculation – just like panels and batteries losing capacity with age.
  • Inverters are optimised for running close to their rated power. A Polish winter means running at a few per cent of it, where the inverter’s own losses dominate.
  • Annual production is a poor measure of payback: on a sunny June day, when RCE prices are negative and batteries are full, the production counter keeps turning but earns nothing.
  • With a small microinverter system, a battery makes no sense for me yet. I hope batteries designed as an add-on to microinverters, or for dynamic tariffs, will appear.

Instead of a battery, I shift consumption to the hours when energy is cheap – with the help of my Android app for RCE energy prices.

Source: my thread on elektroda.pl (in Polish) – Zużycie energii przez falowniki hybrydowe – ile wynosi w trybie gotowości? (February 2025).